SP LINK | Performance Monitoring
88
|
Doc #OI0005 Rev26 2020
Battery Management Tab
If the SP PRO is connected to and communicating with a battery that has a Battery Management System (BMS)
then the
BATTERY MANAGEMENT
tab provides you with the available battery information.
The BATTERY MANAGEMENT section shows information about the entire battery bank whilst the MODULE
STATUS section displays information about the individual battery modules within the battery bank
Charge Current Limit
: The maximum charge current allowed at the time
Discharge Current Limit
: The maximum discharge charge current allowed at
the time
Charge Voltage Limit
: The maximum charge voltage allowed at that time
Battery Current
: The battery current at that time. Positive current is charging,
negative is discharging.
State of Charge
: The battery SoC as read from the BMS.
BMS Model
: The model number of the BMS or battery connected to the
SP PRO
State of Health
Indicates how much of the battery has been used.
Alarms and Warnings
: Displays any alarms or warnings generated by the
BMS.
MODULE STATUS
The module status section provides advance diagnostic information about the battery system and is used for
advanced diagnoses of any faults. It is only available when there are more than one battery module connected
into the system and when the BMS has the facility to provide the information. This section is greyed out when
this information is not available from the BMS.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...