SP LINK | Alert Messages
112
|
Doc #OI0005 Rev26 2020
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
Unit - Output
Capacitor life
expired.
Shutdown. No AC output possible.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Unit - Ouput
Capacitor life expired
cleared
Above condition has cleared
Unit - Output Mode
button fault - button
stuck down
Stuck button on the front panel of the
inverter. If fault persists contact service
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Power Module -
Current Limit Shutdown
Occurs after multiple power module
current limits. Inverter will stay
shutdown until a reset or power cycle
has been performed. Caused by
multiple disturbances in the system or
installation fault.
Check that the grid supply or
generator is stable. If problem
persists then contact your
installer to check the AC wiring
and the quality of either the grid
power or the generator supply.
Unit - Power Module -
Current Limit Shutdown
Cleared
Above condition has cleared
Unit - Power Module -
Low 14V Shutdown
Hardware Fault within the inverter.
Inverter will not run.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Power Module
- Low 14V Shutdown
cleared
Above condition has cleared
Unit - Power Module 1 -
Factory defaults loaded
Caused by hardware glitch. If event
persists then contact Service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Power Module 2 -
Factory defaults loaded
Caused by hardware glitch. If event
persists then contact Service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Power Supply
Shutdown
Hardware Fault within the inverter.
Inverter will not run.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Power Supply
Shutdown cleared
Above condition has cleared
Unit - Real Time Clock
- Did not interrupt
There is a fault in the inverter’s Real
Time Clock. Inverter will need a
service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Real Time Clock
- Reading newer time
There is a fault in the inverter’s Real
Time Clock. Inverter will need a
service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Real Time Clock
- Reading older time
There is a fault in the inverter’s Real
Time Clock. Inverter will need a
service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Real Time Clock
- Reading same time
There is a fault in the inverter’s Real
Time Clock. Inverter will need a
service.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Self Test Fault -
Auto Zero
Power up Self test fault. Inverter will
not start. Inverter hardware fault.
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Self Test Fault
cleared - Auto Zero
Above condition has cleared
Unit - Self Test Fault -
Power Module
Inverter failed Power Up self test.
There is an inverter fault. Inverter will
not start
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Self Test Fault
cleared - Power
Module
Above condition has cleared
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...