SP LINK | Configuration Settings
64
|
Doc #OI0005 Rev26 2020
The SP PRO can help you to manage the system by advising you when certain output
levels have been exceeded.
AC Load Energy Output
selects the output that will be
asserted when the daily energy consumption exceeds
Energy Assert Level
setting.
AC Load Power Output
selects the output that will be asserted when the AC load on
the system exceeds the
Power Assert Level
for 30 seconds. Conversely the output is
de-asserted when the AC load drops below the
power Assert Level
for 30 seconds.
For example let’s assume the system has been designed to provide 10 kilowatt hours a
day and any load exceeding 5 kilowatts is considered excessive.
In the example on the right,
AC Load Energy Output
has been set to Digital Control
Output 1 and this output will be activated when the daily usage reaches 9 kilowatt
hours, as programmed into
Energy Assert Level
.
When set in this way the inverter will advise you, but asserting Digital Control Output 1,
when you are approaching the design limit of the system and allow you to choose if you
wish to modify the power consumption for the remainder of the day. Similarly
AC Load
Power Output
has been allocated to Digital Control Output 2 which will be activated if
the AC load on the system exceeds the
Power Assert Level
of 4.5 kW for 30 seconds.
External Regulator Bypass Output
can be used to control a relay that will bypass the
solar or wind generator regulator to allow the full renewable output to be forwarded to
the battery or exported to the grid.
The
External Regulator Control Output
provides a signal to drive an external solar
regulator
The
AC Coupled Inverter Output
drives an external solid state relay to control when
the AC Coupled inverter feeds to the grid, local AC Load and battery bank. This is
suitable for switching any Grid feed inverter. This setting is only available for Solar
Hybrid (grid connected) configurations.
Any generic AC Coupling is best controlled via AC Frequency. See
System settings Generic AC Coupling. The
AC Coupled Inverter Output
is a legacy setting retained for backward compatibility only.
Zero Percent Output
setting is configured automatically when the ABB Solar inverter
is selected in a Managed AC Coupled Solar configuration. This is for display only and
cannot be changed. Only the ABB PVI grid inverter (no longer sold) uses this output.
The ABB UNO range of Selectronic Certified grid inverters (current range) do not use
this output.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...