SP LINK | Configuration Settings
40
|
Doc #OI0005 Rev26 2020
AC Source Settings
The next tab in our settings menu is the AC Source tab. In this section we are able to change important settings
relating to either the generator or the mains voltage. We use the words AC Source rather than Generator or
Grid power as the SP PRO can be used in a variety of applications which include either of those AC supplies.
There are five sub-tabs within this section:
•
AC INPUT
, relates to general settings that apply if either a generator or the mains grid are used as input power.
•
POWER QUALITY / DRM
. Grid settings for compliance to AS4777.2-2015. power quality modes.
•
GENERATOR AUTO START
relates to conditions that will start the generator automatically.
•
GENERATOR SCHEDULE START
allows programming of scheduled run times for the system.
•
GENERATOR CONTROLLER SETTINGS
is used to set up parameters that relate to the motor generator.
AC Input
This tab allows you to change the conditions under which the AC Input will be utilised by the SP PRO and
transferred through to the AC Load.
Max AC Voltage, 10 min avg
. This setting is only used in a Solar Hybrid system. For off grid systems set it to
the maximum value of 264V. If the 10 minute average of AC Source Voltage goes above this value then the
SP PRO will disconnect from the AC Source. The default of 255V is suitable for Australia. Set this to 248V for
New Zealand.
Reconnect Delay
In a Solar Hybrid system, the time the AC Source is in tolerance before re connecting to the
grid. This delay does not apply to off grid or mobile systems. The defaults as shown are for Australia and NZ.
Min AC Voltage
and
Max AC Voltage
. These parameters are set as
a percentage of the Nominal AC Voltage setting (under the Inverter
tab). If the AC Source voltage goes outside these limits the SP PRO
will disconnect from the AC Source. The defaults (as shown) are for
Australia and NZ.
Min AC Frequency
and
Max AC Frequency
. The parameters are
set as a percentage of the Nominal AC Frequency setting (under
the Inverter tab). If the AC Source frequency goes outside these
limits the SP PRO will immediately disconnect from the AC Source.
The defaults (as shown) are for Australia . For NZ. set the Min AC
Frequency to -10 (45Hz).
THE PRIMARY SOURCE
configurations set the AC voltage and frequency at which the AC Source will
disconnect and the reconduction time for the grid.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...