SP LINK | Alert Messages
Doc #OI0005 Rev26 2020
|
111
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
Unit - AC Source
Contactor Fault -
Contactor stuck closed
- Earth Neutral link not
present
The AC Source contactor has a fault
and has not opened when expected.
This has also caused a EN fault. If
an external contactor is installed then
there is a fault in this section.
Contact your installer to check
all the wiring and components
for the external AC contactor
and its configuration. If the
system does not have an
external AC Source contactor
and if problem persists, your
inverter will need a service.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Unit - AC Source
Contactor Fault cleared
- was closed - EN Link
not present
Above condition has cleared
Unit - AC Source
contactor fault - inverter
volts detected at AC
Source
There are AC volts from the inverter
output appearing on the AC Source
terminals. Indicates either a fault in the
AC Source contactor or a fault in the
system wiring.
Contact your installer to remove
all connections to the AC load
terminals. If Alert persists
then your inverter has a stuck
contactor and will need a
service. Contact Selectronic
service at http://www.selectronic.
com.au/service/
Unit - AC Source
contactor fault cleared
Above condition has cleared
Unit - Alarm Silence
button fault - button
stuck down
Stuck button on the front panel of the
inverter. If fault persists contact service
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Control PCA
Factory defaults loaded
The user has initiated a “Load Defaults”
from the front panel of the inverter.
Unit - Generator button
fault - button stuck
down
Stuck button on the front panel of the
inverter. If fault persists contact service
For persistent fault, contact
Selectronic service at http://
www.selectronic.com.au/service/
Unit - Hi DC Voltage
Fault
Battery voltage has risen to an
abnormally high level. Normally caused
by a fault in the battery, the battery
wiring or the battery fusing.
Call installer to check for faulty
cells in the battery bank or
for poor battery connections
between cells and between
battery bank and SP PRO.
Unit - Hi DC Voltage
Fault cleared
Above condition has cleared
Unit - Instant Hi DC
Voltage Fault
Battery voltage has risen to an
abnormally high level. Normally caused
by a fault in the battery, the battery
wiring or the battery fusing.
Call installer to check for faulty
cells in the battery bank or
for poor battery connections
between cells and between
battery bank and SP PRO
Unit - Instant Hi DC
Voltage Fault cleared
Above condition has cleared
Unit - Instant Low DC
Voltage Fault
Battery voltage has dropped to an
abnormally low level. Normally caused
by a fault in the battery, the battery
wiring or the battery fusing.
Call installer to check for faulty
cells in the battery bank or
for poor battery connections
between cells and between
battery bank and SP PRO
Unit - Instant Low DC
Voltage Fault cleared
Above condition has cleared
Unit - Loading
Configuration Settings
has timed out - retrying
The configuration settings that were
sent from SP LINK have taken much
longer than expected. Try again
Check communications link from
SP LINK to SP PRO inverter. Try
the same process with a direct
USB connection.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...