SP LINK | Using SP LINK
Doc #OI0005 Rev26 2020
|
29
Step 3
If
Automatically restart SP PRO if firmware update is successful
was not checked then the SP PRO
must be restarted to complete the firmware update.
WARNING: During the restart AC LOAD will be interrupted.
There are two Restart options:
Click
Restart SP PRO Now
.
The SP PRO will restart and the Firmware Update window will close after the SP PRO has restarted. The
SP PRO will revert to Idle mode by default.
OR
Set the
Scheduled Restart Time
(in 24hr format) when a few minutes of interruption in power is least
inconvenient.
Click
Set Scheduled Restart
.
The SP PRO is now set to restart at that time and will continue to operate normally.
(If you change your mind about the scheduled restart time, click Cancel Scheduled Restart, then set a new
value. Or if you click
Restart SP PRO Now
, the inverter will restart immediately and any scheduled restart will
be disabled.)
Click Close.
At the scheduled time, the SP PRO will restart, appear to be off for a few minutes, then resume operation as
it was prior to being restarted.
Firmware Update is now complete.