SP LINK | Alert Messages
110
|
Doc #OI0005 Rev26 2020
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
System - Power
Module - Current Limit
Shutdown
There has been a major disturbance
in the system and the hardware
protection has tripped. Inverter will
shutdown momentarily then come back
on
An occasional fault of this
type is OK. Continuous faults
indicate a system wiring fault
or a very poor AC Source such
as malfunctioning generator.
Contact your installer to
diagnose and remedy the
system fault
System - Power
Module - Current Limit
Shutdown cleared
Above condition has cleared
System - Reset
Normal Reset occurs at power up and
after firmware update (Reset buttons).
For a persistent fault, contact
your installer.
System - Sealed
Battery Type defaults
loaded
The user has initiated a “Load Defaults”
from the front panel of the inverter.
System - Service
defaults loaded
The user has initiated a “Load Defaults”
from the front panel of the inverter.
System -
Synchronisation Fail -
AC Source unsuitable
The connected generator has an
unstable voltage or frequency and
the inverter cannot synchronise to it.
Generator needs repair or replacing.
Contact your installer or
generator supplier to carry out
a service on the generator or to
replace the faulty generator.
System -
Synchronisation Fail -
Cleared for retry
Above condition has cleared
System - Synchronised
Overload Shutdown
Inverter has shutdown from over
current when connected and
synchronised to the AC Source.
Caused by a disturbance in the AC
Source voltage or distorted AC Source
voltage.
Fault indicates a poor AC
Source voltage waveform.
Contact your installer if
continuous faults persist to
change the
Grid Quality
setting
in Service Settings to Poor.
Service
Settings> Grid
Quality
System - Synchronised
Overload Shutdown
cleared
Above condition has cleared
System - System
Scheduler defaults
loaded
Occurs when the settings become
corrupt and factory defaults need to
be loaded. Site settings will need to be
loaded back into the inverter.
If fault persists contact your
installer.
Unit - AC Source
Contactor Fault -
Contactor stuck closed
The AC Source contactor has a fault
and has not opened when expected. If
an external contactor is installed then
there is a fault in this section.
Contact your installer to check
all the wiring and components
for the external AC contactor
and its configuration. If the
system does not have an
external AC Source contactor
and if problem persists, your
inverter will need a service.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Unit - AC Source
Contactor Fault cleared
- was closed
Above condition has cleared
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...