SP LINK | Configuration Settings
Doc #OI0005 Rev26 2020
|
65
The
ABB / SelectSun Ground Fault Alarm Output
can only be used in a Managed
AC coupled system using ABB or SelectSun grid inverters. This output will become
active when any of the ABB or SelectSun grid inverters in the system develops a
ground fault. This output is set to the last Ground Fault Alarm Message received.
The SP PRO SILENCE ALARM button does not deactivate this output.
If you are using an external contactor
External AC Contactor Control Output
provides a control signal for actuating the contactor coil. See AC Source AC Input to
Enable the External Contactor/CT functionality.
This control is also used to provide a grid failure alarm. The output is active during a
grid outage.
AC Source in Tolerance Output
configures an output to become active when the AC
Source voltage and frequency are in tolerance according to the settings in AC Source
/ AC Input tab. This output was used in a legacy mutiphase configuration where it is
a requirement for all phases to disconnect from the AC Source when one or more
phases are out of tolerance. Using this output L2-Secondary and L3-Secondary
inverters can signal L1-Primary via the Grid Available Input that they are in tolerance
before L1-Primary connects all phases to the AC Source.
This output is a legacy setting that is only used in legacy three phase systems. This
setting is not required in a three phase Powerchain system.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...