SP LINK | Alert Messages
Doc #OI0005 Rev26 2020
|
105
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
Service - Fan Speed
Alert - Speed lower
than expected - Check
Fan
Cooling fan is running too slow. Check
for fan fault or obstruction.
Clean fan filter in the base of
the unit with a soft brush to
remove any dirt or obstruction.
If problem persists then power
down the SP PRO inverter
following the shutdown
procedure provided beside the
inverter. Remove fan guard
and check fan for obstructions.
Check fan can spin freely. If
problem still persists, contact
your installer to install a new fan.
Service - Fan Speed
Alert cleared - Speed
as expected
Above condition has cleared
Service - Output
Capacitor Life Alert -
Replace capacitors
The Output filter Capacitors are
close to the end of their service life.
Recommend Inverter returned to
service for capacitor replacement.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Service - Output
Capacitor Life Alert
cleared
Above condition has cleared
Service - Output
Capacitor life end -
Replace capacitors
The Output Capacitors within the
SP PRO have reached end of life.
Return Inverter to service for
capacitor replacement.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Service - Output
Capacitor life end
alert cleared.
Above condition has cleared
Service - Power
Module 1 Capacitor
Life Alert - Life at or
above 95%
The internal capacitors have reach
the end of their rated life. Recommend
inverter returned to Service for
capacitor replacement.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Service - Power
Module 1 Capacitor
Life Alert cleared
Above condition has cleared
Service - Power
Module 2 Capacitor
Life Alert - Life at or
above 95%
The internal capacitors have reach
the end of their rated life. Recommend
inverter returned to Service for
capacitor replacement.
Contact Selectronic service at
http://www.selectronic.com.au/
service/
Service - Power
Module 2 Capacitor
Life Alert cleared
Above condition has cleared
System - AC coupled
frequency ramp
invoked
1. Managed AC coupled system -
Indicates loss of control so Inverter
ramps its output frequency to 55 Hz to
cause a AS4777 disconnect to “kick off”
the AC Coupled Inverters
2. Generic AC coupled system –
Normal operation when grid has failed
and inverter running stand alone.
Occurs when the charge target current
or voltage is exceeded.
.If you have a Managed
AC coupled system with a
Selectronic Certified grid
inverter, contact your installer to
come and check all the RS485
cables and wireless devices
between the SP PRO inverter
and the Selectronic Certified grid
inverter.
System - AC coupled
frequency ramp
invoked off
Above condition has cleared
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...