SP LINK | Alert Messages
100
|
Doc #OI0005 Rev26 2020
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
Generator Controller -
Low Fuel Alert cleared
The Generator Low Fuel input has
been cleared
Inputs/Outputs -
Generator Low
Fuel input
Generator Controller
- No Fuel Alert - Stop
generator
The Generator No Fuel input has been
asserted. Generator will be stopped if it
is running
Fill generator fuel tank
Inputs/Outputs
- Generator No
Fuel input
Generator Controller -
No Fuel Alert cleared
The Generator No Fuel input has
been cleared. Generator will start again
as required
Inputs/Outputs
- Generator No
Fuel input
Generator Controller -
Stopped due to no AC
Volts Fault
The Inverter has stopped the generator
as there is no AC volts present at the
inverter. Caused by either a wiring
fault, tripped CB or faulty generator.
Call your installer or
appropriately qualified personnel
to check the AC Source
voltage at the SP PRO when
the generator is running. If no
voltage is present, then they
need to trace the voltage back to
the generator to find the wiring
fault.
Generator Controller -
Stopped due to no AC
Volts Fault Cleared
Above condition has cleared
Inverter - AC Source
out of phase On
Only applies to three phase or Split
phase systems. The phase rotation
or phase sequence on the AC Source
input is incorrect. Caused by wiring
fault on the AC Source input - Phase
rotation or phase angle is incorrect.
Call your installer or
appropriately qualified personnel
to check all AC Source wiring
and AC Source supply for
correct voltage, phase and
phase rotation.
Inverter - AC Source
out of phase Off
Above condition has cleared
Inverter - AC Source
out of tolerance Beeper
On
When the AC Source Disconnect
Beeper is enabled and the AC Source
is outside the set limits (as set in AC
Source > AC Input tab setting) this
alarm will be raised
Normal operation. Alerting the
user that the grid supply has
either failed or it is too high or
too low.
System >
AC Source
Disconnect
Beeper
Inverter - AC Source
out of tolerance Beeper
Off
Above condition has cleared
Inverter - DC Shutdown Inverter has shut down from Low
Battery Voltage
Firstly, reduce all the loads on
the system to the minimum.
Check that all the charging
sources such as PV solar
and generator charging are
functioning correctly. Call
installer to check for faulty cells
in the battery bank or for poor
battery connections between
cells and between battery bank
and SP PRO
Inverter-DC
shutdown
(group) >
Inverter 0% load
and Inverter
100% Load
Inverter - DC Shutdown
cleared - Recovery
Voltage reached
The battery voltage has risen above
the shut down voltage to the Recovery
Voltage
Inverter-DC
shutdown
(group) >
Recovery
Voltage
Inverter - Low AC Alert
The AC output of the inverter is low,
normally due to power overload.
Inverter shutdown is imminent.
Start turning off loads and if
problem persists with little or no
load on the system, call your
installer to check for overload
or short circuits on the AC load
circuits.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...