System Settings
In this section we will look at how the SP PRO works with the whole system. Whether the SP PRO will
automatically recover from system faults, how it will alert you of problems and how it links with the computer
and other communication devices.
The SP PRO is configured to recognise, and report, a number of events that can cause
damage to the system, such as overloads, low voltage batteries. These events can be
announced by a beeper within the SP PRO.
The Alarm -
Beeper
, may be set to:
Enabled - Beeper will activate at any time
Locked Out - Beeper will not activate during the Lock Out period. Set a
Lockout Start
Time
and a
Lockout End Time.
Beeper will activate after lock out if existing alarm still persists. Disabled -
Beeper will not activate for any alarms.
The
AC Source disconnect beeper
provides an alert signal (five short beeps), once
per minute, if the SP PRO is not synchronised to the AC Source. This is disabled
by default and must be Enabled if you wish the system to signal that it is running on
battery supply during grid outages.
The Year to Date feature of the unit is used to monitor the systems performance on an
annual basis. You can choose the start date of that year with
“Year to Date” Rollover
Date
.
This could be the day you installed it, the first day of the year or another date
that is relevant to the installation.
Through
Detailed Data Log Interval
you can choose how often an entry is made. A
short interval of 1 minute will give more detailed information, but for only four days. A
long interval of 30 minutes will give less detail but 120 days of records. A 15 minute
setting records for 60 days and gives a good balance between detail and the number
of days recorded.
Содержание SP PRO 2i Series
Страница 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Страница 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Страница 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Страница 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...