CANopen Field Bus
88
Operating Manual XCx 300 / 500 / 540 Version 09/08
7.6
Expansion Module XF-CAN
The module is used to expand the XCx 300 and the XCx 540. The
module is equipped with following features:
One CANopen field bus interface
Correspond to CAN Application Layer for industrial application
CAL, data transfer layer equal ISO 11898 und CAN 2.0 A+B
communication profil CiA DS-301
7.6.1
Displays and Connections
Display
LED Colour
L1
not used
L2
not used
L3
CAN Network status
off
CAN State Prepared
green
on
CAN State Operational
flashing
CAN State Preoperational
red
on
Bus Off
flashing
CAN Error
L4
CAN Module status
green
on
CAN Stack initialized
flashing
CAN Configuration invalid
red
on
Control unit not ready or serious error
flashing
Error in control unit
Connector X41
Pin
Designation
1
nc
not connected
2
CAN_L
3
V-
Ground
4
nc
not connected
5
Drain
Shield optional
6
V-
Ground
7
CAN_H
8
nc
not connected
9
V+
Power supply
7.6.2
Technical data
Basic data
Interface
CANopen
Connection system
Subminiature type D, 9-pin, socket