PROFIBUS-DP Modules
Operating Manual XCx 300 / 500 / 540 Version 09/08
133
13.7
PROFIBUS-DP Configuration Data
File ProConOS.INI section DPxx
; DP parameter Definitionen:
[DP00]
; e.g. card# 0
; any description
DESCRIPTION = Profibus DPS #0 (XCx5 series)
BUS_ADDR = 2
; 0..126
MASTER_FCONF = 1
; the master force slaves configuration
; 1 = yes (default)/ 0 = no
MASTER_FCONF parameter:
0:
the master configuration data will be compared with the
configuration stored in the file DPSconf0x.ini
1:
the master forces the slave configuration
(the master configuration data are accepted)
Note
The actual XDP configuration is stored in the file
/ram0/OS/LOG/Sysinfo.txt.
Standard Module Configuration
DP Slave: IO area: 0..72
No. Offset Number Byte /Word
Input / Output
Consistency
0
0
4
B
I
-
1
0
4
B
O
-
2
4
4
B
I
-
3
4
4
B
O
-
4
8
16
B
I
c
5
8
16
B
O
c
6
24
16
B
I
c
7
24
16
B
O
c
8
40
16
W
I
c
9
40
16
W
O
c