SLM Drive Module XP-SLM
Operating Manual XCx 300 / 500 / 540 Version 09/08
117
11.1.3
Technical data for SLM drive module XP-SLM
Basic data
Article No.
503 383 32-M
Number of controllable NC axes
up to 4 axes
Electrical data
Power consumption of internal power
supply
typ. 2 W
Isolation
yes, by optocouplers
Supply voltage external
+24V-EXT, GND-EXT
Voltage
24V DC ± 20% max. 5% residual ripple
Power consumption
1,3 W
Serial SLM interface
COM1+, COM1-; COM2+, COM2-; COM3+, COM3-; COM4+, COM4-;
Number
4
Physics
RS 485; 2.5 Mbaud
Protocol
Control Techniques ASIC CT2239-003
Hardware Enable
HWEN1; HWEN2; HWEN3; HWEN4
Number
4
Switching level
H level
+24V-EXT - 0.5 V
L level
1 V
Output current
0.5 A
Signal delay
<300
μs (hardware)
Encoder inputs
A, /A, B, /B, NULL, /NULL
Number
2
Physics
RS422
Max. input frequency
2 MHz
Interrupt inputs
INT+, INT-
Number
2
Switching level
H level = +11 V to +30 V
L level = -30 V to +5 V
Input current
min. H level (+11 V)
≥ 2 mA
max. L level (+5 V)
≤ 2 mA
typ. (+24 V) 8 mA
max. (+30 V)
≤ 15 mA
Signal delay
<100 ns (hardware)
Triggering
flank triggering
Accessories
XP-SLM-K1-3,5
3.5m connecting cable from the XP-SLM module to the drive (10-strand, Harting
connector at one end)
Order no.: 506 383 85