Quick Introduction
Operating Manual XCx 300 / 500 / 540 Version 09/08
43
Meaning of parameters:
-ip192.168.1.2
= IP address of XCx
-TO2000
= Time Out 2000 ms
u=target
= Username
pw=target
= Password
All other settings remain unchanged.
5.4.4
Compiling a project and sending to the XCx
Select
Code/Make
to compile the project.
(or <F9> or
Make
button, see arrow)
The progress of compiling is displayed in the message window
below.
Error messages, warnings and other information are displayed
here.
Click the selection box for error, warning, etc., to display the
message in more detail.
If errors are displayed, you can jump directly to the line of the PLC
program that caused the error by double-clicking in the error line.
Send the project via the Ethernet connection.
1. Click on the
Project Control Dialog
button (see arrow).
2. Click on the
Download
button in the XCx control dialog to open
the
Download
dialog window.
3. Under project, select
Download
again, overwrite the existing
project in the XCx.
4. Use the
Cold
(cold start) button in the control dialog to start the
program on the XCx. The yellow PLC RUN LED lights up.