The PLC
102
Operating Manual XCx 300 / 500 / 540 Version 09/08
9.2.2
Changing operating states with MULTIPROG
You can use the graphic user interface of MULTIPROG to control
when program execution on the PLC starts and stops. The buttons for
changes which are not possible in the current operating state are
shaded in the project control dialog.
Starting program execution
State change
from
to
Button in control
dialog
Description of what happens
Stop
Run
Cold start
All data is initialized
SPG 1 is called
All user tasks are activated
Program execution activated
Stop
Run
Warm start
Only non-buffered data is initialized
SPG 0 is called
All user tasks are activated
Program execution activated
Stop
Run
Hot start
No data is initialized
All user tasks are activated
Program execution activated
Not available when you start program execution for
the first time after downloading
Stopping program execution
State change
from
to
Button in control
dialog
Description of what happens
Run
Stop
All user tasks are deactivated when their operating
cycle is complete
SPG 2 is called
Process map memory outputs are written
Program execution stops
Physical outputs are set to zero or preferred shut-off
state
General reset
State change
from
to
Button in control
dialog
Description of what happens
Stop
Power
on
The project is deleted
General reset