10
Preparing for installation
Model name for combination
AM380JXVAGH1
AM400JXVAGH1
AM420JXVAGH1
AM440JXVAGH1
AM460JXVAGH1
Number of individual outdoor units
2
2
2
2
3
Combined outdoor
unit
AM080JXVAGH
AM100JXVAGH
AM120JXVAGH
2
AM140JXVAGH
1
AM160JXVAGH
1
AM180JXVAGH
AM200JXVAGH
1
AM220JXVAGH
1
1
2
1
AM240HXVAGH
AM260HXVAGH
1
Rated capacity
Cooling (kW)
106 .6
112 .8
117 .6
123 .2
128 .8
Heating (kW)
119 .7
126 .9
132 .3
138 .6
144 .9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
53 .3
56 .4
58 .8
61 .6
64 .4
Maximum (kW)
138 .6
146 .6
152 .9
160 .2
167 .4
Maximum number of connectable
indoor units
64
64
64
64
64
Model name for combination
AM480JXVAGH1
AM500JXVAGH1
AM520JXVAGH1
AM540JXVAGH1
AM560JXVAGH1
Number of individual outdoor units
3
3
3
3
3
Combined outdoor
unit
AM080JXVAGH
AM100JXVAGH
AM120JXVAGH
1
1
1
1
1
AM140JXVAGH
1
AM160JXVAGH
1
AM180JXVAGH
1
AM200JXVAGH
1
AM220JXVAGH
1
1
1
1
2
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
135 .2
140 .2
145 .6
151 .2
156 .8
Heating (kW)
152 .1
157 .5
163 .8
170 .1
176 .4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
67 .6
70 .1
72 .8
75 .6
78 .4
Maximum (kW)
175 .8
182 .3
189 .3
196 .6
203 .8
Maximum number of connectable
indoor units
64
64
64
64
64
DVM S HE_IM_DB68-05461A-08_EN.indd 10
2017-03-24 오후 1:38:15
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...