Symptoms for abnormal operation of the 4way valve
- Abnormal noise during compressor operation, Increase in the suction temperature .
❇
❇
Symptoms for abnormal operation of the Main EEV
- It is not possible to control the superheat (SH)
- It is not possible to secure a DSH of higher than 20K
❇
❇
For more information, see the troubleshooting in the service manual .
• If service valve (ball valve) check is required, corresponding outdoor unit will display the error .
• If service valve (ball valve) check is required, auto detection mode will be terminated . Check service valve (ball valve) of
gas pipe and liquid pipe at the same time when checking service valve (ball valve) .
• When 4way valve, Main EEV detection is needed, run heating trial operation for more than 1 hour and analyze the data
to check for a problem .
• If there's frost formed in outdoor unit or the outdoor unit is operating in defrost operation, it may be hard to detect
problem normally . In this case, perform Trial operation or Forced defrost operation to eliminate the frost, and then
perform Auto Trial Operation again .
• If the operation range is not within guaranteed range, error may occur even though the product is normal .
• To replace a component or inspect the PBA, be sure to cut off the power supply first . If inspection must be performed
with the power supply on, exercise extra care to prevent electric shock .
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 113
2017-03-24 오후 1:38:49
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...