101
ENGLISH
Setting key operation and checking the view mode with tact switch
K1
K2
K3
K4
< A type >
< B type >
K1 control
KEY operation
Display on segment
Press and hold
1 time
Auto trial operation
“K” “K” “BLANK” “BLANK”
K1 (Number of
press)
KEY operation
Display on segment
1 time
Refrigerant charging in Heating mode
“K” “1” “BLANK” “BLANK”
2 times
Trial operation in Heating mode
“K” “2” “BLANK” “BLANK”
3 times
Pump out in Heating mode (Outdoor unit address 1)
“K” “3” “BLANK” “1”
4 times
Pump out in Heating mode (Outdoor unit address 2)
“K” “3” “BLANK” “2”
5 times
Pump out in Heating mode (Outdoor unit address 3)
“K” “3” “BLANK” “3”
6 times
Pump out in Heating mode (Outdoor unit address 4)
“K” “3” “BLANK” “4”
7 times
Vaccuming (Outdoor unit address 1)
“K” “4” “BLANK” “1”
8 times
Vaccuming (Outdoor unit address 2)
“K” “4” “BLANK” “2”
9 times
Vaccuming (Outdoor unit address 3)
“K” “4” “BLANK “ “3”
10 times
Vaccuming (Outdoor unit address 4)
“K” “4” “BLANK” “4”
11 times
Vaccuming (All outdoor units)
“K” “4” “BLANK” “A”
12 times
End Key operation
-
DVM S HE_IM_DB68-05461A-08_EN.indd 101
2017-03-24 오후 1:38:45