97
ENGLISH
Installing and setting the option with tact switch and explanation of the functions
Setting the option
1 . Press and hold K2 to enter the option setting . (Only available when the operation is stopped)
- If you enter the option setting, display will show the following . (If you have set the 'Emergency operation for
compressor malfunction', 1 or 2 will be displayed on Seg 4 .)
- Seg 1 and Seg 2 will display the number for selected option .
- Seg 3 and Seg 4 will display the number for set value of the selected option .
2 . If you have entered option setting, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and
select the desired option . (Refer to pages 81~83 for the Seg number of the function for each option)
Example)
3 . If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and
change the function for the selected option . (Refer to pages 81~83 for the Seg number of the function for each
option)
Example)
4 . After selecting the function for options, press and hold the K2 switch for 2 seconds . Edited value of the option will
be saved when entire segments blinks and tracking mode begins .
• Edited option will not be saved if you do not end the option setting as explained in above instruction .
CAUTION
❇
❇
While you are setting the option, you may press and hold the K1 button to reset the value to previous setting .
❇
❇
If you want to restore the setting to factory default, press and hold the K4 button while you are in the option
setting mode .
- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored
setting is saved . Press and hold the K2 button . When the segments shows that tracking mode is in progress,
setting will be saved .
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Emergency
operation for
compressor
malfunction
Individual
0
0
0
0
Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state .
0
1
Set compressor 1 as
malfunction state
0
2
Set compressor 2 as
malfunction state
DVM S HE_IM_DB68-05461A-08_EN.indd 97
2017-03-24 오후 1:38:45
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...