Pipe insulation
Insulate the distribution header
X
f
Fix the distribution header with a cable tie and cover the connected part .
X
f
Insulate the distribution header and the welded part and wrap the connected part with
an adhesive insulation tape to prevent dew formation .
Insulation
Adhesive insulation tape
Insulate the refrigerant
pipe
Insulate the
distribution
header
Insulate after welding a stopper
Adhesive insulation tape
X
f
Fix the distribution header with a hanger after insulating it .
Insulating the branch joint
X
f
Tightly attach the insulator, provided with the branch joint, to the separately purchased insulator . Wrap the
connected part with an insulator (separately purchased item) that has thickness of at least 10mm .
X
f
Use an insulator that resist heat up to 120°C . Wrap the branch joint with an insulation that has thickness of at least
10mm .
Fix securely without any gap .
Provided
Insulator
Fix securely
without any gap .
Pipe insulator
(Separately
purchased item)
Pipe insulator
(Separately
purchased item)
150mm
Branch
joint
Thickness of the insulator (Separately purchased
item) should be thicker than 10mm .
Insulation tape (Separately purchased item)
Pipe insulator (Separately purchased item)
Pipe
❇
❇
Attach the adhesive insulation
tape to the pipe, as shown in the
picture, after insulating the pipe .
DVM S HE_IM_DB68-05461A-08_EN.indd 90
2017-03-24 오후 1:38:42
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...