Automatic refrigerant amount detection function
This function checks amount of refrigerant in the system through refrigerant amount detection operation
Start
Press the Tact switch "K2" 5 times
Check the amount of refrigerant
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal / Excessive /
Insufficient
Judgment not
available
Judgment not
available
Connect S-Net Pro2
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal / Excessive /
Insufficient
Satisfy the temperature condition
Satisfy the temperature condition
Check the amount of refrigerant
Input S-CHECKER signal
Check stability
Check stability
End
Yes
No
No
Yes
❇
❇
After refrigerant amount detection is finished, if you see “K9 Ed” on the display and cannot check the refrigerant
amount from the S-net pro and S-checker, it means insufficient degree of supercooling .