Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch .
❇
❇
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the
outdoor unit (A), apply the pipe size (A) .
Indoor unit capacity (kW)
Pipe size (mm)
Liquid pipe
Low pressure gas pipe
High pressure gas pipe
15 .0 kW and below
Ø 9 .52
Ø 15 .88
Ø 15 .88
Over 15 .0 kW ~ 22 .4 kW and below
Ø 19 .05
Over 22 .4 kW ~ 28 .1 kW and below
Ø 22 .22
Ø 19 .05
Over 28 .1 kW ~ 33 .6 kW and below
Ø 12 .70
Ø 28 .58
Over 33 .6 kW ~ 45 .0 kW and below
Ø 22 .22
Over 45 .0 kW ~ 50 .4 kW and below
Ø 15 .88
Over 50 .4 kW ~ 63 .3 kW and below
Ø 28 .58
Over 63 .3 kW ~ 70 .3 kW and below
Ø 34 .92
Over 70 .3 kW ~ 98 .4 kW and below
Ø 19 .05
Over 98 .4 kW ~ 105 .5 kW and below
Ø 41 .28
Over 105 .5 kW ~ 135 .2 kW and below
Ø 34 .92
Over 135 .2 kW ~ 169 .0 kW and below
Over 169 .0 kW
Ø 22 .22
Ø 53 .98
Ø 41 .28
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity .
Indoor unit capacity (kW)
Pipe size (O.D. mm)
Liquid pipe
Gas pipe
6 .0 kW and below
Ø 6 .35
Ø 12 .70
7 .2 kW ~ 16 .0 kW and below
Ø 9 .52
Ø 15 .88
20kW ~ 23 .0 kW and below
Ø 9 .52
Ø 19 .05
Over 23 .0 kW
Ø 9 .52
Ø 22 .22
DVM S HE_IM_DB68-05461A-08_EN.indd 43
2017-03-24 오후 1:38:20
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...