63
ENGLISH
Installing the distribution header
1 . Select the reducer that fits the diameter of the pipe .
<Gas side>
Socket
Pipe *
To indoor unit
Pipe*
Socket
To outdoor unit
<Liquid side>
Socket
Pipe*
To indoor unit
Pipe*
Socket
To outdoor unit
Provided item
❇
❇
Pipe : Separately purchased item
2 . If the number of connected indoor unit is fewer than ports on the distribution header, block the unused ports with
caps .
<Liquid side>
Case of blocking the unused
distribution header ports
Connect in
order
Welding part
Provided
item
<Gas side>
Case of blocking the unused
distribution header ports
Connect in
order
• For A~J type distribution header :
Connect the distribution header to the connection pipe with the provided reducer .
• For K~Z type distribution headers :
Cut the provided socket, according to the diameter of the connection pipe, before connecting it .
Over 10~15mm
NOTE
• Connect the indoor units in order, while respecting the direction of the arrow shown in the illustration .
• When indoor units are connected to same distribution head, indoor unit must be connected in order of
their capacity, from largest to smallest .
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 63
2017-03-24 오후 1:38:30
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...