Refrigerant pipe installation
3 . Install the distribution header horizontally .
X
f
Install the distribution header horizontally so that its ports does not face down .
Below ±10°
Horizon line
Socket
Distribution header
Pipe
(Separately purchased item)
Below ±15°
Horizon line
Horizon line
< Liquid side >
Below ±15°
Horizon line
Below ±10°
Horizon line
< Gas side >
Installing the branch joint between outdoor units
Installation of outdoor joints
Do not install the outdoor
joint in this direction .
Liquid pipe
High pressure
gas pipe
Gas pipe
❇
❇
High pressure gas pipe only applies to the H/R product .