Refrigerant pipe installation
Allowable length of the refrigerant pipe and the installation examples
H/P
Classification
Single Installation
Module installation
Installing only with
Y-joint
Branch joint
Outdoor unit
Indoor unit
Branch joint
Outdoor unit
Indoor unit
Installing with Y-joint
and distribution
header
Branch joint
Distribution header
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Distribution header
Branch joint
Installing only with
distribution header
Outdoor unit
Indoor unit
Distribution header
Outdoor unit
Indoor unit
Distribution header
Classification
Example
Remarks
Maximum
allowable
length of
pipe
Outdoor unit ~
Indoor unit
Actual
length
(Equivalent
length)
200m and
below
(220m and
below)
Installing only
with Y-joint
a+b+c+d+e+f+g+p ≤
200m(220m)
Equivalent length
Y-joint: 0 .5 m,
Distribution
header: 1 m
Installing with
Y-joint and
distribution
header
a+b+h ≤ 200m (220m),
a+i+k ≤ 200m (220m)
Installing only
with distribution
header
a+i ≤ 200m (220m)
Total length
of pipe (m)
1,000 m or
less
Installing only
with Y-joint
a+b+c+d+e+f+g+h+i+
j+k+l+m+n+p ≤ 1000m
-
Installing with
Y-joint and
distribution
header
a+b+c+d+e+f+g+h+i+j+k
≤ 1000m
-
Installing only
with distribution
header
a+b+c+d+e+f+g+h+i
≤ 1000m
-
Outdoor unit
~ Outdoor
unit (Module
installation)
Pipe length
10 m or less
x ≤ 10 m, y ≤ 10m, z ≤ 10 m
Equivalent
length
13 m or less
x ≤ 13 m, y ≤ 13m, z ≤ 13 m
DVM S HE_IM_DB68-05461A-08_EN.indd 58
2017-03-24 오후 1:38:28
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...