Connecting the power terminal
X
f
Connect the cables to the terminal board with solderless ring terminals .
X
f
Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external
force is not applied to the terminal .
X
f
Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board .
X
f
Tighten the terminal screws by complying rated torque value . If the terminal is loose, fire can occur due to arc heat
generation and if the terminal is too tight, terminal board could get damaged .
Power cable protection tube
The place where the sheath of the power
supply cable is removed .
Connector
Solderless ring
terminal
Thin cable
Thick cable
Cable tie
When connecting two cables to one terminal,
separate the solderless terminal up and down to
prevent it from getting loose . Place the thin cable
upward and the thick cable downward . Fix the
power cable with a cable tie .
Screw
Tightening torque for
terminal (N∙m)
M4
1 .2~1 .8
Single phase (220-
240 V) power cable
M8
5 .5~7 .3
3 phase (380-415 V)
power cable
• When removing the outer sheath of the power supply cable, be careful not to scratch the inner sheath of
the cable .
• Make sure that more than 20mm of the outer sheath of the indoor unit power and communication cable
are inside the electrical component box .
• Install the communication cable separately from power cable and other communication cables .
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 79
2017-03-24 오후 1:38:38
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...