54
Refrigerant pipe installation
2 . Connecting refrigerant pipe for outdoor unit
Classification
Front side connection
Right/left (and bottom) side connection
Working process
• First, remove the piping cover from the
outdoor unit .
• Separate the knock-out hole that you are
going to use . If you separate the knock-
out hole that is going to be unused, small
animals such as squirrels and rats may get
into the unit through the hole .
• Fix the bottom side of the piping cover first
and then fix the top part of it .
• Separate the knock-out hole at the bottom
side of the unit and install the pipe .
• After installing and insulating the pipe, close
up the remaining holes . If not, small animals
such as rats and squirrels may get inside the
unit .
H/P
Liquid side
pipe
Gas side
pipe
Gas side
pipe
Liquid side
pipe
H/R
High pressure
gas pipe
Liquid side
pipe
Low pressure
gas pipe
Liquid side
pipe
Low pressure
gas pipe
High pressure
gas pipe
DVM S HE_IM_DB68-05461A-08_EN.indd 54
2017-03-24 오후 1:38:24
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...