49
ENGLISH
Classification
Model name of
indoor unit
Number of units
Unit amount of
refrigerant (kg/EA)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
①
②
①
×
②
∑(
①
×
②
)
Indoor unit (
ⓑ
)
4way cassette
(AM071FN4DEH
✴
)
5
0 .45
2 .25
ⓑ
4 .66
4way cassette
(AM112FN4DEH
✴
)
2
0 .57
1 .14
Neo forte
(AM028FNTDEH
✴
)
1
0 .27
0 .27
MCU
2
0 .5
1
- Total amount of refrigerant (
ⓐ
+
ⓑ
) = 11 .965+4 .66 = 16 .625 (kg)
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter (mm)
Minimum thickness (mm)
Temper grade
Ø 6 .35
0 .70
Annealed
Ø 9 .52
0 .70
Ø 12 .70
0 .80
Ø 15 .88
1 .00
Ø 19 .05
0 .90
Drawn
Ø 22 .22
0 .90
Ø 25 .40
1 .00
Ø 28 .58
1 .10
Ø 31 .75
1 .10
Ø 34 .92
1 .20
Ø 38 .10
1 .35
Ø 41 .28
1 .43
Ø 44 .45
1 .60
Ø 50 .80
2 .00
Ø 53 .98
2 .10
• For pipes larger than Ø 19 .05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used . If a
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause
personal injury .
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 49
2017-03-24 오후 1:38:22
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...