98
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Cooling capacity
correction
Main
0
1
0
0
7-9 (Factory default in case of
A type PBA)
Targeted evaporation
temperature [°C] .
(When low temperature
value is set, discharged air
temperature of the indoor unit
will decrease)
0
1
5-7 (Factory default in case of
B type PBA)
0
2
9-11
0
3
10-12
0
4
11-13
0
5
12-14
0
6
13-15
Capacity
correction for
heating
Main
0
2
0
0
3 .0 (Factory default)
Targeted high pressure [MPa] .
(When low pressure value
is set, discharged air
temperature of the indoor unit
will decrease)
0
1
2 .5
0
2
2 .6
0
3
2 .7
0
4
2 .8
0
5
2 .9
0
6
3 .1
0
7
3 .2
0
8
3 .3
Current
restriction rate
Individual
0
3
0
0
100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease .
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection
interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the
product is being installed in
humid area such as near river
or lake
Fan speed
correction for
outdoor unit
Individual
0
6
0
0
Factory default
0
1
Increase fan speed
Increase the outdoor unit's fan
speed to maximum value
Setting outdoor unit option switch and key function
DVM S HE_IM_DB68-05461A-08_EN.indd 98
2017-03-24 오후 1:38:45
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...