96
Setting outdoor unit option switch and key function
Setting outdoor unit option switches : B TYPE
X
f
Setting outdoor install option
Step
Button
Display
Description
Note
Start
Outdoor unit address
Quantity of indoor units
Main unit?
No
No
Yes
Yes
Save
Heat recovery?
Quantity of MCUs
Outdoor unit address
Step1
Outdoor unit
display
Setting required
-
Step2
Press (K1+K2)
for 2 seconds
Unit address
for module
combination
00: Main unit
K4 x 1 time
01: Sub1 unit
K4 x 2 times
02: Sub2 unit
K4 x 3 times
03: Sub3 unit
Step3
If it is main unit, go to step4 .
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Quantity of indoor units
Step4
Press K1
Ready to set
-
Step5
K2 x n times
X
Tens digit (0 ~ 6)
Ex) 03: 3 units
64: 64 units
K4 x n times
X
Ones digit (0 ~ 9)
* K4: Press for 2 seconds - automatic detection of indoor units’ quantity
Step6
If it is heat recovery model, go to step 7 .
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Quantity of MCUs * Heat recovery model only
Step7
Press K1
Ready to set
-
Step8
K2 x n times
X
Tens digit (0 ~ 1)
Ex) 03: 3 units
16: 16 units
K4 x n times
X
Ones digit (0 ~ 9)
* K4: Press for 2 seconds - automatic detection of MCUs' quantity
Step9
K2: long
Save
Restart
* Press K1 for 2 seconds to exit without save regardless of setting step .
DVM S HE_IM_DB68-05461A-08_EN.indd 96
2017-03-24 오후 1:38:45
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...