45
ENGLISH
X
f
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch .
❇
❇
However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe connected to the
outdoor unit (D), apply the pipe size (D) .
• Y-joint
Classification
Model name
Specification (kW)
Y-joint (E)
MXJ-YA1509M
15 .0 kW and below
MXJ-YA2512M
Over 15 .0 kW ~ 40 .0 kW and below
MXJ-YA2812M
Over 40 .0 kW ~ 45 .0 kW and below
MXJ-YA2815M
Over 45 .0 kW ~ 70 .3 kW and below
MXJ-YA3419M
Over 70 .3 kW ~ 98 .4 kW and below
MXJ-YA4119M
Over 98 .4 kW ~ 135 .2 kW and below
MXJ-YA4422M
Over 135 .2 kW
Y-joint (E)
(Only H/R)
MXJ-YA1500M
22 .4 kW and below
MXJ-YA2500M
Over 22 .4 kW ~ 70 .3 kW and below
MXJ-YA3100M
Over 70 .3 kW ~ 135 .2 kW and below
MXJ-YA3800M
Over 135 .2 kW
DVM S HE_IM_DB68-05461A-08_EN.indd 45
2017-03-24 오후 1:38:21
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...