Single installation
X
f
Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant .
X
f
If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and
liquid side service valve . Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor
PCB .
Gas side
Scale
R-410A (Inject
liquid refrigerant)
Liquid side
Vacuum port
Manifold gage
Service valve
Outdoor unit