61
ENGLISH
Classification
Example
Remarks
Maximum
allowable
height
difference
Outdoor unit ~
Indoor unit
Pipe length
110 m / 110 m
Note 1)
H1 ≤ 110 m / 110 m
Indoor unit ~
Indoor unit
40 m or less
H2 ≤ 40 m
But, when AM
✴✴✴✴
NQDEH
✴
/ AM
✴✴✴
JNV
✴
is installed, H2 is 15
m or less .
Indoor unit ~
Indoor unit
(in one MCU)
15 m or less
H3 ≤ 15 m
MCU ~ MCU
30 m or less
H4 ≤ 30 m
Maximum
allowable
length after
branch
joint
First branch
joint ~ Farthest
Indoor unit
Pipe length
45 m or less
Installing only with MCU
g+j ≤ 45 m
Installing with MCU
and Y-joint
b+h+k ≤ 45 m
l+m+q ≤ 45 m
l+r ≤ 45 m
45 ~ 90 m
Note 2)
Required conditions must be satisfied
EEV Kit
Model name
Remarkers
EEV kit ~
Indoor unit
Actual pipe
length
2 m
MEV-E24SA
1 indoor
Apply to products without EEV
(Wall mount & ceiling)
MEV-E32SA
20 m or less
MXD-E24K132A
2 indoor
MXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K222A
MXD-E32K300A
❇
❇
Please refer to the EEV Kit manual .
Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If the height difference is over
40m, contact your local dealer for more information .) but when the indoor unit is located at lower level than outdoor unit, allowable
height difference is 110m (If the height difference is over 50m, need to decide whether to install PDM kit or not .)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Note 2) Required condition
Classification
Condition
Example
First branch
joint ~ Farthest
Indoor unit
45 m ≤ b+h+k, l+m+q, l+r ≤ 90 m : Size of the branch liquid and
low pressure gas pipes (b, l, m) must be increased by 1 grade .
Total length of
extended pipe
If the size of pipe (main pipe), between the first branch joint
and the outdoor unit, is not increased by 1 grade, a+(b+l+m)
x2+c+d+e+f+g+h+i+j+k+n+o+p+q+r ≤ 1000 m
If the size of pipe (main pipe), between the first branch joint
and the outdoor unit, is increased by 1 grade, (a+b+l+m)
x2+c+d+e+f+g+h+i+j+k+n+o+p+q+r ≤ 1000 m
MCU ~ Each
indoor unit
c+d, c+e, c+f, g, h+i, h+j, h+k, n, o, p, q, r ≤ 45 m
Difference between the distance of the outdoor unit to the farthest indoor unit and
nearest indoor unit ≤ 45 (a+b+h+k) - (a+b+c+d) ≤ 45
Note 3) For indoor units to which no MCU is connected, be sure to set their options to “Cooling only indoor unit,” and then connect them to a
low pressure gas pipe and a liquid pipe . Be sure to combine the cooling only indoor units so that their total capacity becomes 50% or
less of the total capacity of all indoor units .
Note 4) In case of connecting more than one indoor unit in one MCU Port, the below indoor units cannot be combined . ERV plus
(AM
✴✴✴
FNKDE
✴✴
), OAP duct(AM
✴✴✴
JNEPE
✴✴
), Hydro Unit HE(AM
✴✴✴
FNBD
✴✴
), Hydro Unit HT(AM
✴✴✴
FNBF
✴✴
), AHU kit
(MXD-K
✴✴✴
AN, MCM-D
✴✴✴
N)
Note 5) In case of connecting two MCU ports with Y-joint, the indoor units cannot be combined to more than one .
DVM S HE_IM_DB68-05461A-08_EN.indd 61
2017-03-24 오후 1:38:30
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...