Safety precautions
Please follow the following safety information for safety of the installer and the user .
❇
❇
DVM S air conditioner uses R-410A refrigerant .
• When using R-410A, moisture or foreign substances may affect the performance and reliability of the
product . Safety precautions must be obeyed when installing the refrigerant pipe .
• The designed maximum pressure of the system is 4 .1MPa and therefore select appropriate material and
thickness according to the regulations .
• R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when filling the
refrigerant . (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product
malfunction .)
❇
❇
You must connect the indoor units for R-410A refrigerant . Refer to product catalog to find out the models
names for connectable indoor units . (If you connect the indoor units that are not designed for R-410A, it
cannot operated normally .)
❇
❇
After completing the installation and trial operation, explain to the user how to use and maintain the product . Also,
hand over this installation manual so that it can be stored by the user .
❇
❇
Manufacturer is not responsible for the incidents occurred by improper installation . Installer is responsible for
any installation related claims from the user occurred by neglecting warnings and cautions stated in this manual .
(Installer will be responsible for any service charges that may occur)
❇
❇
Generally, system air conditioners should not be relocated after installation . But when it has to be relocated for
inevitable reasons, please contact Samsung’s qualified dealers for system air conditioners .
WARNING
• Hazards or unsafe practices that may
result in severe personal injury or death
.
CAUTION
• Hazards or unsafe practices that may
result in minor personal injury (to installer/user) or
property damage
.
SEVERE WARNING SIGNS
Consult qualified installer or dealer for installation.
X
X
When installation is done by unqualified person, problems such as water leakage, electric shock or fire may occur .
Installation work must be done properly according to this installation manual.
X
X
When installation is not done properly, it may cause water leakage, electric shock or fire .
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding
allowable safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the
installation.
X
X
When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents .
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and
it may cause injury.
Use the supplied accessories, specified components and tools for the installation.
X
X
Do not use the pipe and the installation product used for the R-22 refrigerant .
X
X
Failure to use the specified components can cause product fall down, water leakage, electrical shock, and fire . (The
pipe and flare components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
X
X
If the place cannot support its weight, the outdoor unit may fall down and it may cause injury .
DVM S HE_IM_DB68-05461A-08_EN.indd 3
2017-03-24 오후 1:38:14
Содержание AM080JXVHGH/EU
Страница 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Страница 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Страница 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Страница 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...