Module installation
<Case 3>
O
ver 500
O
ver 500
O
ver 600
Over 100 Over 100
Over 100
Over 100
Over 100
Over 100 Over 100
Over 100
Front side
Front side
<Case 1>
<Case 2>
O
ver 200
O
ver 100
O
ver 300 (S2)
O
ver 500 (S1)
Over 100
Over 100
Over 100
Over 300
Over 400
Over 400
Height of
the wall is
unlimited
Front
side
Front side
❇
❇
For <Case 1> or <Case 3>
• Height of the wall on the front side should not be higher than 1500mm .
• Height of the wall on the air inlet side should not be higher than 500mm .
• Height of the wall on the side is not limited .
• If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded distance] should be added to the service space (S1, S2) .
1500
h1
500
h2
Fron
t side
Air inlet side
(Unit : mm)
S1+h1/2
S2+h2/2