Function Parameters
79 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.00
Phase loss
protection
0x000~0x111
LED ones:
0:
Input phase loss software protection disable
1:
Input phase loss software protection enable
LED tens:
0:
Output phase loss protection disable
1:
Output phase loss protection enable
LED hundreds:
0:
Input phase loss hardware protection disable
1:
Input phase loss hardware protection enable
0x010
○
P11.01
Sudden power
loss frequency
decreasing
function selection
0:
Disabled
1:
Enabled
0
○
P11.02
Frequency
decreasing
ratio at sudden
power loss
Setting range: 0.00Hz/s~P00.03 (the Max. frequency)
After the power loss of the grid, the bus voltage drops to the
sudden frequency-decreasing point, the inverter begins to
decrease the running frequency at P11.02, to make the
inverter generate power again. The returning power can
maintain the bus voltage to ensure a rated running of the
inverter until the recovery of power.
Voltage degree
220-230V
400V
Frequency-decreasing
point at sudden power
loss
260V
460V
Note:
1. Adjust the parameter properly to avoid the stopping
caused by inverter protection during the switching of the grid.
2. Disable input phase loss protection to enable this function.
10.00
Hz/s
○
P11.03
Overvoltage
stall protection
0:
Disabled
1:
Enabled
1
○