Function Parameters
71 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
changing ratio
P08.47
Action
selection for
frequency
settings on
power off
0x000~0x111
LED ones
: Action for digital adjustable frequency on power
off
0
: Save on power off
1
: Clear on power off
LED tens
: Action for MODBUS frequency setting on power
off
0
: Save on power off
1
: Clear on power off
LED hundreds
: Action for other-mode frequency setting on
power off
0
: Save on power off
1
: Clear on power off
0x000
○
P08.48
High bit of
initial power
consumption
This parameter is used to set the original value of the power
consumption.
The original value of the power consumption =P08.48*1000+
P08.49
Setting range of P08.48: 0~59999 kWh (x1000)
Setting range of P08.49:0.0~999.9 kWh
0 kWh
○
P08.49
Low bit of initial
power
consumption
0.0 kWh
○
P08.50
Magnetic flux
braking
coefficient
This function code is used to enable magnetic flux.
0:
Invalid.
100~150:
the bigger the coefficient, the stronger the braking
strength.
The inverter can slow down the motor by increasing the magnetic
flux. The energy generated by the motor during braking can be
transformed into heat energy by increasing the magnetic flux.
The inverter monitors the state of the motor continuously
even during the magnetic flux period. So the magnetic flux
can be used in the motor stop, as well as to change the
rotation speed of the motor. Its other advantages are:
Brake immediately after the stop command. It does not need
to wait the magnetic flux weaken.
The cooling is better. The current of the stator other than the
rotor increases during magnetic flux braking, while the
cooling of the stator is more effective than the rotor.
0
○
P08.51
Input power
factor of the
inverter
This function code is used to adjust the displayed current of
the AC input side.
Setting range: 0.00~1.00
0.56
○
P09 Group PID control