Function Parameters
39 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range: 0.0~3600.0s (valid when P01.19=2)
P01.21
Restart after
power off
This function can enable the inverter start or not after the
power off and then power on.
0: Disabled
1: Enabled
, if the starting need is met, the inverter will run
automatically after waiting for the time defined by P01.22.
0
○
P01.22
Waiting time of
restart after
power off
The function determines the waiting time before the
automatic running of the inverter when powering off and then
powering on.
Setting range: 0.0~3600.0s (valid when P01.21=1)
1.0s
○
P01.23 Start delay time
The function determines the brake release after the running
command is given, and the inverter is in a stand-by state and
wait for the delay time set by P01.23
Setting range: 0.0~60.0s
0.0s
○
P01.24
Delay time of
the stopping
speed
Setting range: 0.0~100.0s
0.0s
○
P01.25
0Hz output
selection
Select the 0Hz output of the inverter.
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
0
○