Function Parameters
65 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
CV30 inverters define four groups of ACC/DEC time which
can be selected by P5 group. The first group of ACC/DEC
time is the factory default one.
Setting range: 0.0~3600.0s
on model
P08.01
DEC time 2
Depends
on model
○
P08.02
ACC time 3
Depends
on model
○
P08.03
DEC time 3
Depends
on model
○
P08.04
ACC time 4
Depends
on model
○
P08.05
DEC time 4
Depends
on model
○
P08.06
Jogging
running
frequency
This parameter is used to define the reference frequency
during jogging.
Setting range: 0.00Hz ~P00.03 (the Max. frequency)
5.00Hz
○
P08.07
Jogging
running ACC
time
The jogging ACC time means the time needed if the inverter
runs from 0Hz to the Max. Frequency.
The jogging DEC time means the time needed if the inverter
goes from the Max. Frequency (P00.03) to 0Hz.
Setting range: 0.0~3600.0s
Depends
on model
○
P08.08
Jogging running
DEC time
Depends
on model
○
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping frequency,
the inverter will run at the edge of the jumping frequency.
The inverter can avoid the mechanical resonance point by
setting the jumping frequency. The inverter can set three
jumping frequencies. But this function will be invalid if all
jumping points are 0.
Setting range: 0.00~P00.03 (the Max. frequency)
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz
○
P08.11
Jumping
frequency 2
0.00Hz
○
P08.12
Jumping
frequency
range 2
0.00Hz
○
P08.13
Jumping
frequency 3
0.00Hz
○
P08.14
Jumping
frequency
range 3
0.00Hz
○
P08.15 Traverse range This function applies to the industries where traverse and
convolution function are required such as textile and
chemical fiber.
0.0%
○
P08.16
Sudden
0.0%
○