56 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
27~30:
Reserved
P06.05
Polarity
selection of
output
terminals
The function code is used to set the pole of the output terminal.
When the current bit is set to
0
, output terminal is
positive
.
When the current bit is set to
1
, output terminal is
negative
.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
Reserved
Y1
Setting range: 0~F
0
○
P06.06
Y1 open delay
time
The setting range: 0.000~50.000s
0.000s
○
P06.07
Y1 off delay
time
The setting range: 0.000~50.000s
0.000s
○
P06.10
RO1 switching
on delay time
The function code defines the corresponding delay time of
the electrical level change during the programmable terminal
switching on and off.
The setting range: 0.000~50.000s
0.000s
○
P06.11
RO1 switching
off delay time
0.000s
○
P06.12
RO2 switching
on delay time
0.000s
○
P06.13
RO2 switching
off delay time
0.000s
○
P06.14
AO1 output
selection
0:
Running frequency
1:
Setting frequency
2:
Ramp reference frequency
3:
Running rotation speed
4:
Output current (relative to twice the inverter rated current)
5:
Output current (relative to twice the motor rated current)
6:
Output voltage
7:
Output power
8:
Set torque value
9:
Output torque
10:
Analog AI1 input value
11:
Analog AI2 input value
12:
Analog AI3 input value
13:
High speed pulse HDI input value
0
○
P06.15
AO2 output
selection
0
○