Communication protocol
107 - 140
The command means that the master write data to the inverter and one command can write one data other
than multiple dates. The effect is to change the working mode of the inverter.
For example, write 5000 (1388H) to 0004H from the inverter with the address of 02H, the frame structure is as below:
RTU master command message (from the master to the inverter)
START T1-T2-T3-T4
ADDR 02H
CMD 06H
High bit of writing data address
00H
Low bit of writing data address
04H
High bit of data content
13H
Low bit of data content
88H
CRC CHK low bit
C5H
CRC CHK high bit
6EH
END T1-T2-T3-T4
RTU slave response message (from the inverter to the master)
START T1-T2-T3-T4
ADDR 02H
CMD 06H
High bit of writing data address
00H
Low bit of writing data address
04H
High bit of data content
13H
Low bit of data content
88H
CRC CHK low bit
C5H
CRC CHK high bit
6EH
END T1-T2-T3-T4
7.3.1.3 Command code 08H for diagnosis
Meaning of sub-function codes
Sub-function Code
Description
0000
Return to inquire information data
For example: The inquiry information string is same as the response information string when the loop
detection to address 01H of driver is carried out.
The RTU request command is:
START T1-T2-T3-T4
ADDR 01H
CMD 08H