Function Parameters
75 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
between the reference and the feedback unless it reaches the
internal integral limit. When the trend between the reference and
the feedback changes, it needs more time to offset the impact of
continuous working and the integration will change with the trend.
1: Stop integral adjustment
when the frequency reaches
the upper and low limit. If the integration keeps stable, and
the trend between the reference and the feedback changes,
the integration will change with the trend quickly.
LED tens (P00.08 is 0)
0: Same with the setting direction
; if the output of PID
adjustment is different from the current running direction, the
internal control will output 0 forcedly.
1: Opposite to the setting direction
LED hundreds (P00.08 is 0)
0: Limit to the maximum frequency
1: Limit to A frequency
LED thousands:
0: A+B frequency, buffer ACC/DEC is invalid
for the main
reference A frequency source
1: A+B frequency, buffer ACC/DEC is valid
for the main
reference A frequency source and the ACC/DEC is
determined by time set in P08.04
P09.14
Proportional
gain at low
frequency (Kp)
0.00~100.00
1.00
○
P09.15
PID command
of ACC/DEC
time
0.0~1000.0s
0.0s
○
P09.16
PID output filter
time
0.000~10.000s
0.000s
○
P10 Group Simple PLC and multi-step speed control
P10.00
Simple PLC
means
0: Stop after running once
. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once
. After finish a
signal, the inverter will keep the running frequency and
direction of the last run.
2: Cycle running
. The inverter will keep on running until
receiving a stop command and then, the system will stop.
0
○
P10.01
Simple PLC
memory
0: Power loss without memory
1: Power loss memory
. PLC record the running stage and
0
○