44 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
electromotion
torque
0:
Keypad setting upper-limit frequency (P03.20 sets P03.18
and P03.21 sets P03.19)
1:
Analog AI1 setting upper-limit torque
2:
Analog AI2 setting upper-limit torque
3:
Analog AI3 setting upper-limit torque
4:
Pulse frequency HDI setting upper-limit torque
5:
MODBUS communication setting upper-limit torque
6~8:
Reserved
Note:
Setting mode 1~8,100% corresponds to three times of
the motor current.
P03.19
Upper-limit
setting of
braking torque
0
○
P03.20
Electromotion
torque
upper-limit
keypad setting The function code is used to set the limit of the torque.
Setting range: 0.0~300.0% (motor rated current)
180.0%
○
P03.21
Braking
torque
upper-limit
keypad setting
180.0%
○
P03.22
Weakening
coefficient in
constant power
zone
The usage of motor in weakening control.
Function code P03.22 and P03.23 are effective at constant power.
The motor will enter into the weakening state when the motor runs at
rated speed. Change the weakening curve by modifying the
weakening control coefficient. The bigger the weakening control
coefficient is, the steeper the weak curve is.
Setting range of P03.22: 0.1~2.0
Setting range of P03.23: 10%~100%
0.3
○
P03.23
The lowest
weakening point
in constant
power zone
20%
○
P03.24
Max. voltage
limit
P03.24 set the Max. Voltage of the inverter, which is
dependent on the site situation.
Setting range: 0.0~120.0%
100.0%
◎
P03.25
Pre-exciting
time
Pre-activate the motor when the inverter starts up. Build up a
magnetic field inside the motor to improve the torque performance
during the starting process. Setting time: 0.000~10.000s
0.300s
○
P03.26
Weakening
proportional
gain
Setting range: 0~8000
1200
○
P03.27
Speed display
selection of
vector control
0:
Display at the actual value
1:
Display at the setting value
0
○
P04 Group SVPWM control