Function Parameters
69 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Voltage
220V
380V
Range
375~400V
685~750V
P08.39
Cooling fan
running mode
Set the operation mode of the cooling fan.
0: Normal mode
, after the rectifier receives operation
command or the detected temperature of module is above
45
℃
, or the module current is above 20% of the rated
current, the fan rotates.
1: The fan keeps on running after power on
(generally for
the site with high temperature and humidity)
0
○
P08.40 PWM selection
0x000~0x0021
LED ones
: PWM mode selection
0: PWM mode 1
, three-phase modulation and two-phase
modulation
1: PWM mode 2,
three-phase modulation
LED tens
: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1,
the carrier
frequency will limit to 1kHz or 2kHz if it exceeds 2kHz at low
speed
1: Low-speed carrier frequency limit mode 2
, the carrier
frequency will limit to 4kHz if it exceeds 4kHz at low speed
2: No limit
for the carrier frequency at low speed
0x01
◎
P08.41
Over comission
selection
LED ones
0:
Invalid
1:
Valid
LED tens (for factory commissioning)
0: Light over comission; in zone 1
1: Heavy over comission; in zone 2
The default value of the inverters of 1PH 230V/3PH 400V
≤
2.2kW and 3PH 220V
≤
0.75kW) is 00;
The default value of the inverters of 3PH 400V
≥
4kW and
3PH 220V
≥
1.5kW is 01.
0x00
◎
0x01
P08.42
Keypad data
control setting
0x0000~0x1223
LED ones:
frequency enable selection
0:
Both
∧
/
∨
keys and analog potentiometer adjustments
are valid
1:
Only
∧
/
∨
keys adjustments are valid
0x0000
○