Function Parameters
35 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
running and keep in the stand-by state. The starting
frequency is not limited in the lower limit frequency.
Setting range: 0.0~50.0s
P01.03
Braking current
before starting
The inverter will carry out DC braking at the braking current set
before starting and it will speed up after the DC braking time. If
the DC braking time is set to 0, the DC braking is invalid.
The stronger the braking current, the bigger the braking
power. The DC braking current before starting means the
percentage of the rated current of the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
0.0%
◎
P01.04
Braking time
before starting
0.00s
◎
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up and
running.
0: Linear type
The output frequency increases or decreases linearly.
1: S curve
, the output frequency will increase or decrease
according to the S curve
S curve is generally used on the applications of gradual
starting and stopping, such as elevators.
0
◎