74 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range: 0.0~100.0%
P09.09
Output upper
limit of PID
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. Frequency or the Max. Voltage
of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
100.0%
○
P09.10
Output lower
limit of PID
0.0%
○
P09.11
Feedback
offline
detection value
Set the PID feedback offline detection value when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report “PID feedback offline
fault” and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0.0%
○
P09.12
Feedback
offline
detection time
1.0s
○
P09.13
PID adjustment
selection
0x0000~0x1111
LED ones:
0: Keep on integral adjustment
when the frequency achieves
the upper and low limit; the integration shows the change
0x0001
○