Function Parameters
43 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
4:
Analog AI3 setting torque
5:
Pulse frequency HDI setting torque
6:
Multi-step torque setting
7:
MODBUS communication setting torque
8~10:
Reserved
Note
: Setting mode 2~7, 100% corresponds to 3 times of the
motor rated current
P03.12
Keypad setting
torque
Setting range: -300.0%~300.0% (motor rated current)
50.0%
○
P03.13
Torque reference
filter time
0.000~10.000s
0.100s
○
P03.14
Setting source
of forward
rotation
upper-limit
frequency in
torque control
0:
keypad setting upper-limit frequency (P03.16 sets P03.14,
P03.17 sets P03.15)
1:
Analog AI1 setting upper-limit frequency
2:
Analog AI2 setting upper-limit frequency
3:
Analog AI3 setting upper-limit frequency
4:
Pulse frequency HDI setting upper-limit frequency
5:
Multi-step setting upper-limit frequency
6:
MODBUS communication setting upper-limit frequency
7~9:
Reserved
Note
: setting method 1~9, 100% corresponds to the
maximum frequency
0
○
P03.15
Setting source
of reverse
rotation
upper-limit
frequency in
torque control
0
○
P03.16
Torque control
forward
rotation
upper-limit
frequency
keypad defined
value
This function is used to set the upper limit of the frequency.
P03.16 sets the value of P03.14; P03.17 sets the value of
P03.15.
Setting range:0.00 Hz~P00.03 (the Max. output frequency)
50.00
Hz
○
P03.17
Torque control
reverse
rotation
upper-limit
frequency
keypad defined
value
50.00
Hz
○
P03.18
Upper-limit
setting of
This function code is used to select the electromotion and
braking torque upper-limit setting source selection.
0
○