Keypad Operation Procedure
23 - 140
No.
Name
Description
1 State
LED
RUN/TUNE
LED off means the inverter is in the stopping state;
LED blinking means the inverter is in the parameter
autotune state; LED on means the inverter is in the
running state.
FWD/REV
FWD/REV LED
LED off means the inverter is in the forward rotation
state; LED on means the inverter is in the reverse
rotation state
LOCAL/REMOT
LED for keypad operation, terminals operation and
remote communication control
LED off means that the inverter is in the keypad
operation state; LED blinking means the inverter is in
the terminals operation state; LED on means the
inverter is in the remote communication control state.
TRIP
LED for faults
LED on when the inverter is in the fault state; LED off
in normal state; LED blinking means the inverter is in
the pre-alarm state.
2 Unit
LED
Mean the unit displayed currently
Hz Frequency
unit
RPM
Rotating speed unit
A Current
unit
% Percentage
V Voltage
unit
3
Code
displaying
zone
5-figure LED display displays various monitoring data and alarm code such as set
frequency and output frequency.
4
Analog
potentio
meter
When the external common keypad is installed (keypad without the function of
parameter copy), the difference between AI1 in the local keypad and AI1 in the
external keypad is:
When the external keypad AI1 is set to the Min. value, the local keypad AI1 will be
valid and P17.19 will be the voltage of the local keypad AI1; otherwise, the external
keypad AI1 will be valid and P17.19 will be the voltage of the external keypad AI1.
Note
: If the external keypad AI1 is frequency reference source, adjust the local
potentiometer AI1 to 0V/0mA before starting the inverter.