32 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
4: Max (A, B)
: The bigger one between A frequency
command and B frequency is the set frequency.
5: Min (A, B)
: The lower one between A frequency command
and B frequency is the set frequency.
Note:
The combination manner can be shifted by P05
(terminal function)
P00.10
Keypad set
frequency
When A and B frequency commands are selected as
“keypad setting”, this parameter will be the initial value of
inverter reference frequency
Setting range:0.00 Hz~P00.03 (the Max. frequency)
50.00Hz
○
P00.11
ACC time 1
ACC time means the time needed if the inverter speeds up
from 0Hz to the Max. output frequency (P00.03).
DEC time means the time needed if the inverter speeds
down from the Max. Output frequency (P00.03) to 0Hz.
CV30 inverters have four groups of ACC/DEC time which
can be selected by P05. The factory default ACC/DEC time
of the inverter is the first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
Depend
s on
model
○
P00.12
DEC time 1
Depend
s on
model
○
P00.13
Running
direction
selection
0: Runs at the default direction
, the inverter runs in the
forward direction. FWD/REV indicator is off.
1: Runs at the opposite direction
, the inverter runs in the
reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation direction of the
motor. This effect equals to the shifting the rotation direction
by adjusting either two of the motor lines (U, V and W). The
motor rotation direction can be changed by QUICK/JOG on
the keypad. Refer to parameter P07.02.
Note:
When the function parameter comes back to the
default value, the motor’s running direction will come back to
the factory default state, too. In some cases it should be
used with caution after commissioning if the change of
rotation direction is disabled.
2: Forbid to run in reverse direction
: It can be used in
some special cases if the reverse running is disabled.
0
○